• Internal Room comfort is planned for 73° F +/ - 2 and RH not exceeding 60 %

• Each floor has multiple AHU rooms for proper zonalization.

• Occupancy is planned at 80 sqft. / person.

• Computers are considered with 100 W per terminal without any diversity.

• 20 CFM fresh air is considered per person as per ASHRAE standards.

• Each chiller will be 370 TR air-cooled screw chiller.

• Both the primary and secondary pumps will have VFDs.

• The BMS will be designed and installed to operate the chillers and Pumps in the most efficient way.

• A separate treated fresh air machine is planned @ 1 per AHU room.

• Enclosed stair cases will be pressurized